Insulators are designed to fix and insulate wires of power transmission lines with the nominal voltage 330 kV, frequency up to 100 Hz with the air temperature from - 60 to + 50 оС. Insulators are designed to fix and insulate wires of power transmission lines with the nominal voltage 330 kV, frequency up to 100 Hz with the air temperature from - 60 to + 50 оС.
Insulators conform to the requirements of IEC 61109.
Designation
|
Fig.
|
Rated voltage, kV
|
Maximum working voltage, kV
|
Minimum mechanical failing load, kN
|
Spacing, Н,
mm, max
|
Insulation spacing, L,
mm, min
|
Creepage distance,
mm, min
|
Withstand
voltage, kV
|
Weight,
kg, max
|
IEC 61466-1
|
GOST R 55189
|
full lightning impulse
|
switching impulse
|
dry power-frequency
|
wet power-frequency
|
CS 70-1450/7285*
|
ЛК 70/330-И-2
|
1
|
330
|
363
|
70
|
2955
|
2745
|
7285
|
1450
|
1000
|
750
|
650
|
9,5
|
CS 70-1450/9030
|
ЛК 70/330-И-3
|
2
|
9030
|
10,3
|
CS 70-1450/10770
|
ЛК 70/330-И-4
|
3495
|
3285
|
10770
|
11,5
|
CS 120-1450/7285
|
ЛК 120/330-И-2
|
1
|
120
|
2960
|
2745
|
7285
|
9,7
|
CS 120-1450/9030
|
ЛК 120/330-И-3
|
2
|
9030
|
10,5
|
CS 120-1450/10770
|
ЛК 120/330-И-4
|
3500
|
3285
|
10770
|
11,7
|
CS 160-1450/7285
|
ЛК 160/330-И-2
|
1
|
160
|
3300
|
2745
|
7285
|
10,3
|
CS 160-1450/9030
|
ЛК 160/330-И-3
|
2
|
9030
|
10,8
|
CS 160-1450/10770
|
ЛК 160/330-И-4
|
3540
|
3825
|
10770
|
12,0
|
* — There are four types of insulators classified by the end fitting types: TB, SB, ST, TT. Other end fittings are available by a special request.
|
|